Angled sheds with antidrop for vertical installation
For outdoor/indoor installation
Brown colour
Electrical ratings | Dimensional ratings |
||||||||
Type | N. of skirts | Rated voltage (KV) | Impulse voltage (KV Bil) | Dry- Withstand (KV) | Wet- Withstand (KV) | Total creepage (mm.) | Air-distance (mm.) | Max height (mm.) | Max diameter (mm.) |
DC10 | 1 | 2,4 | 35 | 20 | 10 | 65 | 50 | 107 | 75 |
DC15 | 2 | 3,6 | 40 | 24 | 13 | 90 | 55 | 100 | 65 |
DC160 | 2 | 7,2 | 60 | 38 | 20 | 150 | 80 | 157 | 95 |
DC200 | 3 | 12 | 75 | 50 | 28 | 215 | 115 | 178 | 95 |
DC260 | 4 | 17,5 | 95 | 75 | 38 | 280 | 150 | 209 | 95 |
DC300 | 4 | 24 | 125 | 85 | 50 | 330 | 205 | 245 | 115 |
Available variants and materials:
Flange for soldering in fire tinned brass or steel, diameter from 70 to 85 mm.
Thread in tinned brass from M6 to M16 - including ½’’-13th
Stud with bore several diameters
Solid stud with wire already connected
Wire sections: 5 – 10 – 12 – 16 – 25 mm²
Tests performed:
Leak test at 6 bars on 100%
Visual inspection on 100%
Dimension test on sample quantity
Temperature test at 130°C on sample quantity
Cantilever load test from 350N until 750 N – Type test
Traction (tensile) load test at 1500N – Type test
Torque test at 45Nm – Type test