C-TYPES ELECTRICAL/DIMENSIONAL RATINGS |
||||||||||||
Zamber type | Impulse Voltage (kVBIL) | Power frequency withstandvoltage wet-outdoor (kV) | Power frequency withstandvoltage dry-indoor (kV) | Rated Voltage (kV) | Min. creep (mm) | Min. arc distance (mm) | Total height out of the lid (mm) | Weight without wire (kg) | Colour | n. of skirts | Bore dia. (mm) | Diameter of the skirts |
C1 | 60 | 20 | 28 | 7,2 | 132 | 80 | 138 | 0,6 | gray | 2 | 19 | 80 |
C2 | 75 | 28 | 38 | 12 | 225 | 120 | 182 | 0,9 | gray | 4 | 19 | 80 |
C3 | 95 | 38 | 50 | 17,5 | 330 | 160 | 226 | 1,3 | gray | 6 | 19 | 80 |
C4 | 125 | 50 | 70 | 24 | 530 | 215 | 271 | 1,7 | gray | 8 | 19 | 92 |
C45 | 150 | 70 | 80 | 24 | 600 | 240 | 292 | 1,9 | gray | 9 | 19 | 92 |
C5 | 150 | 70 | 80 | 24 | 725 | 260 | 315 | 2,5 | gray | 10 | 19 | 99 |
C6 | 170 | 80 | 95 | 36 | 745 | 300 | 359 | 2,5 | gray | 12 | 19 | 95 |
C8 | 250 | 95 | n.a. | 36 | 1050 | 410 | 468 | 3,6 | gray | 17 | 19 | 95 |
Available variants and materials:
Flange for soldering in fire tinned brass or steel, diameter from 70 to 85 mm.
Flange for TIG/MIG welding in stainless steel, diameter 89 mm.
Thread in tinned brass from M6 to M16 - including ½’’-13th
Stud with bore several diameters
Solid stud with wire already connected
Wire sections: 5 – 10 – 12 – 16 – 25 mm²
Tests performed:
Leak test at 6 bars on 100%
Visual inspection on 100%
Dimension test on sample quantity
Temperature test at 130°C on sample quantity
Dry lightning impulse voltage withstand test (BIL) – Type test
Dry power-frequency voltage withstand test – Type test
Wet power-frequency voltage withstand test following – Type test
Temperature Rise test (250A – 50Hz)– Type test
Cantilever load test from 350N until 750 N – Type test
Traction (tensile) load test at 1500N – Type test
Torque test at 45Nm – Type test