Parallel sheds for horizontal/vertical installation
For outdoor/indoor installation
Grey or brown colour
More than 5.000.000 units installed in 10+ years of product life
BHW-TYPES ELECTRICAL/DIMENSIONAL RATINS |
||||||||||||
Zamber type | Impulse Voltage (kVBIL) | Power frequency withstand voltage wet-outdooor (kV) | Power frequency withstand voltage dry-indoor (kV) | Rated Voltage (kV) | Creepage (mm) | Arc distance (mm) | Total height out of the lid (mm) | Weight without wire (kg) | Colour | n. of skirts | Bore dia. (mm) | Diameter of the skirts (mm) |
BHW S1 | 95 | 38 | 70 | 17,5 | 380 | 160 | 220 (+/-7) | 1,8 | gray/brown | 6 | 19 | 95 |
BHW S3 | 150 | 50 | 85 | 24 | 620 | 240 | 300 (+/-9) | 2,4 | gray/brown | 10 | 19 | 95 |
BHW S5 | 170 | 70 | 100 | 36 | 820 | 300 | 360 (+/-9) | 3,2 | gray/brown | 13 | 19 | 95 |
BHW S7 | 200 | n.d. | n.d. | 36 | 1020 | 360 | 420 (+/-9) | 4,0 | gray/brown | 16 | 19 | 95 |
Available variants and materials:
LT variant for temperatures down to -60°C (standard down to -45°C)
Flange for TIG/MIG welding in stainless steel, diameter 87 or 89 mm.
Already assembled to stainless steel lids of several dimensions
Standard thread in nickel plated brass M16 with bore 8mm. or solid with tinned copper wire wire already connected
Tinned copper wire sections: 5 – 10 – 12 – 16 – 25 mm²
Cap in Stainless steel AISI316
Routine tests performed:
Leak test at 6 bars on 100%
Torque test at 45Nm on 100%
Visual inspection on 100%
Sample tests performed:
Dimension test
Cantilever destructive load
High temperature test at 130°C
Type tests performed:
Dry lightning impulse voltage withstand (BIL)
Dry power-frequency voltage withstand
Wet power-frequency voltage withstand
Temperature rise (250A – 50 Hz)
Radio Influence voltage
Cantilever load test up to 1000N
Cantilever load test up to 1000N under internal pressure of 3 bar
Traction (tensile) load test up to 1500N
Dynamic Cantilever load test
Low temperature test until -60°C with cantilever 50kg.
Low temperature cycle test until -60°C to ambient: 5 times
High temperature test at 90°C for 16h
Temperature cycle test -55°C to ambient temperature
Dynamic current withstand test
Vibration test
Contamination test 500 hrs. (tandelta)